ATM/N - Analog Level Transmitter
PRESSURE MEASURING RANGE (MH20)
1 ... 5, (1) > 5 ... 20 > 20 ... 250
Overpressure 3 bar 3 x FS (≥ 3 bar) 3 x FS
Burst pressure, (2) > 200 bar > 200 bar > 200 bar
Accuracy, (3) (± % FS) ≤ 0.5 / ≤ 0.25 ≤ 0.5 / ≤ 0.25 / ≤ 0.1 ≤ 0.5 / ≤ 0.25 / ≤ 0.1
Thermal shift, (± % FS/°C)
Zero point -5 ... 50°C ≤ 0.06 ≤ 0.03 ≤ 0.015
Span -5 ... 50°C ≤ 0.015 ≤ 0.015 ≤ 0.015
Response time, (typ.) < 1ms / 10 ... 90% FS < 1ms / 10 ... 90% FS < 1ms / 10 ... 90% FS
Long term stability, (4) < 0.5% FS / < 4 mbar < 0.2% FS / < 4 mbar < 0.1% FS / < 0.2% FS
(1) 0.5 mH2O on request
(2) Transducer
(3) Zero based accuracy according to DIN-16086, incl. hysteresis and repeatability at ambient temperature
(4) 1 year (typ. / max.), the long term stability can be improved by ageing (burn-in) the sensor
TEMPERATURE RANGE
Operating temperature -5 ... 80°C (1)
Process temperature -5 ... 80°C (1)
Storage temperature -10 ... 80°C
- Stok Adeti: 2
- Stok Kodu: 91/CV-2